Hi Mark,

The message at 10:47 says the the computer was rebooted at that time. That
is about the only way that I know of that this message would be recorded.

When the TrbCurtail Service is started it does not remember what turbines
were curtailed. It waits 10-minutes after starting before issuing any
commands to calculate a 10-minute average. After the 10 minute startup wait,
the first command output from this program would have released all turbines
that were currently curtailed, and curtailed new turbines as needed to keep
the 10-minute average MW output at the curtailment setpoint.

So at 10:57 any turbines that were curtailed before that time would have been
released.
The curtailment log file Visupro creates at the turbine should be able to
verify this if needed
.

Database:

System
Index Number Date/Time Msg
10843 840006029 6/19/02 10:36 Energy curtailed -< Turbine curtailed
10847 840006250 6/19/02 10:47 TrbCurtail Service Started -< Computer rebooted
10855 840006029 6/19/02 10:47 Turbine Com Established -< Com established to
turbine


Joe






Mark Fisher
07/09/2002 03:07 PM
To: Joe Chapman/EWC/Enron@ENRON
cc: Jeff Duff/EWC/Enron@ENRON

Subject: Curtail200206.db Question

Joe,

Attached is the Curtail200206.db file. I have a question about a sequence of
events. For turbine 840006029 on June 19th the turbine is "Energy curtailed"
(Index = 10843), THEN it has the message "Turbine Com Established" (Index =
10855). Then there are no other messages (for that turbine) until a "Energy
curtailed" message (Index = 11134).

Is there anything I can assume about the time between the curtailment
messages? For example, was the turbine uncurtailed when the com established
message was recorded? Or are did the turbine become uncurtailed and no
message was recorded?

Thanks,
Mark